Agent skill

Fire Life Safety

by Abhinavbwj in Abhinavbwj/Skills-Architects

Comprehensive fire and life safety design expertise covering fire strategy development, compartmentation and fire barrier design, means of egress design including travel distances and stair sizing…

MITAuto-check passed

Install Fire Life Safety

skills CLI
$ npx skills add Abhinavbwj/Skills-Architects --skill fire-life-safety -a claude-code

Project install by default; add -g for ~/.claude/skills/.

GitHub CLI
$ gh skill install Abhinavbwj/Skills-Architects fire-life-safety --agent claude-code

Project scope by default; add --scope user for a personal install. Needs GitHub CLI 2.90.0 or later (public preview).

Manual copy
$ git clone --depth 1 https://github.com/Abhinavbwj/Skills-Architects.git skills-src && mkdir -p .claude/skills && cp -r skills-src/skills/fire-life-safety .claude/skills/fire-life-safety && rm -rf skills-src

Use ~/.claude/skills/ instead of .claude/skills for a personal install. The folder must contain SKILL.md.

Claude Code skills documentation · loads skills from .claude/skills/

Facts

Skill name
fire-life-safety
GitHub stars
296
Token cost
~8.2k tokens
SKILL.md length
4,340 words
Files
2 (incl. references)
Skills in repo
17
Repo updated
First seen
Licence
MIT

At a glance

Comprehensive fire and life safety design expertise covering fire strategy development, compartmentation and fire barrier design, means of egress design including travel distances and stair sizing…

  • Works in 5 steps: Life safety: Ensure all occupants can… → Property protection: Limit fire damage… → Business continuity: Design systems to… → …
  • SKILL.md covers Section 1: Fire Strategy…, Section 2: Compartmentation, Section 3: Means of Egress… and Section 4: Structural Fire…, plus 1 more section
  • Instructions only: no scripts, shell commands, URLs or credentials in SKILL.md

What it does

Fire Life Safety is an agent skill from Abhinavbwj/Skills-Architects. Comprehensive fire and life safety design expertise covering fire strategy development, compartmentation and fire barrier design, means of egress design including travel distances and stair sizing, fire resistance ratings and structural fire protection methods, smoke control systems (natural and mechanical), active fire protection systems (sprinklers, detection, alarm, emergency lighting), fire door specifications, and fire strategy coordination between architect and fire engineer.

Its SKILL.md is about 8.2k tokens, which your agent loads only when the skill is triggered. The skill folder holds 2 other files, including reference files (for example `references/egress-design.md`).

The licence is MIT.

Example prompts

  • “/fire-life-safety”

Workflow steps

5 steps, taken from the first numbered list in SKILL.md.

  1. Life safety: Ensure all occupants can evacuate or reach a place of
  2. Property protection: Limit fire damage to the area of origin or
  3. Business continuity: Design systems to minimize downtime after a fire
  4. Environmental protection: Prevent fire-related contamination of soil,
  5. Firefighter safety: Provide safe access for fire service operations.

What it can do on your machine

Read from SKILL.md and the folder at commit 30a0845. It shows what the files ask for, not the result of running them.

  • Tool permissions

    Pre-approves nothing: there is no allowed-tools line, so your agent's usual permission prompts apply.

    From allowed-tools in the SKILL.md frontmatter.

  • Runs code

    No scripts in the folder and no shell commands in SKILL.md.

    From the folder's file list and the shell code blocks in SKILL.md.

  • Network

    No URLs in SKILL.md.

    From URLs in SKILL.md, links to its own repository left out.

  • Credentials

    Names no API keys, tokens, secrets or passwords.

    From names ending in _API_KEY, _TOKEN, _SECRET, _KEY or _PASSWORD in SKILL.md.

Context cost

Fire Life Safety loads about 8.2k tokens when it runs, and up to ~14k if it reads all its reference files. Until then it costs about 126 tokens; SKILL.md has 4,340 words of instructions outside code blocks.

Always · name and description, kept in context so the agent knows when to use it
~126
When it runs · the whole SKILL.md, loaded when a task matches
~8.2k
With references · SKILL.md plus every file in references/, read only if the agent opens them
~14k

Estimates: characters ÷ 4, the usual rule of thumb; real counts depend on the model's tokenizer. Scripts and assets cost tokens only if the agent reads them.

Safety

Auto-check passed

The automated check found no risky patterns in SKILL.md.

Automated static check — not a guarantee. Review scripts before installing. It scans the text of SKILL.md for risky patterns (piping downloads into a shell, reading credential files, hidden Unicode, destructive commands); files beside SKILL.md are not scanned.

SKILL.md

The full file from Abhinavbwj/Skills-Architects at commit 30a0845, republished under its MIT licence (© Abhinavbwj). 4,340 words, ~8,161 tokens.

Download SKILL.mdSave it as .claude/skills/fire-life-safety/SKILL.md (or your agent's skills folder). This skill also uses 1 other file; get the full folder from GitHub.
name
fire-life-safety
description
Comprehensive fire and life safety design expertise covering fire strategy development, compartmentation and fire barrier design, means of egress design including travel distances and stair sizing, fire resistance ratings and structural fire protection methods, smoke control systems (natural and mechanical), active fire protection systems (sprinklers, detection, alarm, emergency lighting), fire door specifications, and fire strategy coordination between architect and fire engineer.

Fire and Life Safety Design

This skill provides practitioner-grade knowledge of fire and life safety design for architectural practice. It covers the architect's role in fire strategy, compartmentation, egress design, structural fire protection, smoke control, and active fire protection systems. All dimensional values are metric with imperial equivalents where standard practice requires.


Section 1: Fire Strategy Development

The Architect's Role

The architect is the primary coordinator of fire strategy in building design. While fire engineers provide specialist analysis (computational fire modeling, structural fire engineering, smoke control design), the architect is responsible for integrating fire safety into the architectural concept from the earliest design stage.

Fire safety is not an add-on. Buildings that treat fire protection as an afterthought suffer from: compromised spatial quality (corridors widened at the expense of usable space), increased cost (fire-rated construction added where it could have been avoided by better planning), and occupant risk (egress paths that are long, confusing, or difficult to maintain).

Fire Safety Objectives
  1. Life safety: Ensure all occupants can evacuate or reach a place of safety before conditions become untenable. This is the primary objective and is non-negotiable.

  2. Property protection: Limit fire damage to the area of origin or a defined compartment. Relevant for insurance, business continuity, and heritage buildings.

  3. Business continuity: Design systems to minimize downtime after a fire event. Particularly important for: hospitals (defend-in-place), data centers, manufacturing, and critical infrastructure.

  4. Environmental protection: Prevent fire-related contamination of soil, water, and air. Relevant for: chemical storage, waste facilities, sites near waterways.

  5. Firefighter safety: Provide safe access for fire service operations. Firefighting shafts, wet/dry risers, fire command centers, adequate water supply.

Prescriptive vs Performance-Based Approach

Prescriptive approach:

  • Follow code provisions directly (IBC, Approved Document B, NBC, etc.)
  • Advantages: straightforward, well-understood, defensible
  • Limitations: may be overly conservative, may not address novel building configurations, does not account for specific building use patterns

Performance-based approach:

  • Establish fire safety objectives, define design fire scenarios, demonstrate through engineering analysis that objectives are met
  • Methods: computational fire modeling (FDS, CFAST), evacuation modeling (Pathfinder, STEPS, Simulex), structural fire analysis (FEA with fire curves), smoke control analysis (CFD)
  • Advantages: can optimize design, accommodate complex geometries, provide a more accurate risk assessment
  • Limitations: requires specialist fire engineer, peer review, AHJ acceptance

Hybrid approach (most common):

  • Follow prescriptive code for most provisions
  • Use performance-based analysis for specific challenges: atrium smoke control, travel distance extensions, reduced fire resistance periods, alternative egress strategies
Fire Strategy Report Content

A fire strategy report (also called fire safety strategy, fire engineering report, or basis of fire safety design) should include:

  1. Building description: use, occupancy, construction, geometry
  2. Applicable codes and standards
  3. Design fire scenarios (size, location, growth rate)
  4. Compartmentation strategy and fire resistance schedule
  5. Means of escape: travel distances, exit widths, evacuation strategy
  6. Fire detection and alarm design
  7. Sprinkler/suppression system scope
  8. Smoke control strategy
  9. Structural fire protection specification
  10. Fire service access and facilities
  11. Building management fire safety provisions
  12. Drawings: compartmentation plans, egress plans, fire service access plans

Section 2: Compartmentation

Purpose

Fire compartmentation divides a building into distinct zones that contain fire and smoke for a defined period, allowing occupants to evacuate, limiting property damage, and providing safe zones for defend-in-place strategies.

Compartment Sizing

IBC (US):

  • No explicit maximum compartment size for most occupancies (controlled by construction type and area per floor)
  • I-2 smoke compartments: max 2090 m² (22,500 ft²) per smoke compartment per IBC 407.5.1
  • I-3 smoke compartments: max 2090 m² (22,500 ft²) per IBC 408.6

BS 9999 (UK): Maximum compartment sizes by risk profile:

Risk ProfileMax Compartment Floor AreaMax Dimension
A1 (low risk)8,000 m²No limit
A24,000 m²No limit
B12,000 m²No limit
B21,000 m²No limit
C1 (sleeping, low risk)2,000 m²No limit
C21,000 m²No limit
C3 (high dependency)1,000 m²No limit

Approved Document B (England & Wales): Maximum compartment sizes by purpose group:

Purpose GroupHeight < 18 mHeight >= 18 m
Residential (flats)No limit*No limit*
Office2,000 m²2,000 m²
Shop/commercial2,000 m²2,000 m²
Assembly/recreation2,000 m²2,000 m²
Industrial2,000 m²2,000 m²
Storage1,000 m²1,000 m²

(*Flats: each dwelling is a compartment; common corridor/stair protected)

Fire-Rated Construction Types

Fire Barrier (IBC 707):

  • Continuous from floor slab to underside of floor or roof slab above (deck, not ceiling)
  • Used for: occupancy separation, exit enclosures, shaft enclosures, horizontal exits
  • Supports: must be supported by construction with equal or greater FRR
  • Continuity: all joints, penetrations, and openings must be protected

Fire Partition (IBC 708):

  • May terminate at underside of a fire-rated floor/ceiling or roof/ceiling assembly
  • Used for: dwelling unit separation, sleeping unit separation, corridor walls
  • Less stringent than fire barrier (can stop at ceiling if ceiling is rated)

Fire Wall (IBC 706):

  • Structurally independent (remains standing if structure on either side collapses)
  • Extends from foundation to roof (through roof unless roof is fire-rated)
  • Creates separate buildings for code purposes
  • Rating: 2 hr (A, B, E, F-2, M, R, S-2, U), 3 hr (F-1, H-3/4/5, S-1), 4 hr (H-1, H-2)

Smoke Barrier (IBC 709):

  • Continuous membrane from floor to floor, outside wall to outside wall
  • Smoke-tight construction with smoke dampers at duct penetrations
  • 1-hour minimum fire resistance
  • Used for: I-2 smoke compartments, I-3 smoke compartments, ambulatory care smoke compartments
Fire Door Ratings

IBC/UL system (US):

ApplicationDoor RatingWall Rating
Fire wall opening3 hr4 hr
Fire wall opening1.5 hr2 hr
Fire barrier -- exit enclosure1.5 hr2 hr
Fire barrier -- exit enclosure1 hr1 hr
Fire barrier -- occupancy separation1.5 hr2 hr
Fire barrier -- occupancy separation0.75 hr1 hr
Fire partition -- corridor0.33 hr0.5 hr
Fire partition -- corridor0.33 hr1 hr
Smoke barrier0.33 hr1 hr

British Standard / European system:

DesignationIntegrity (min)Insulation (min)Typical Use
FD3030--Corridor doors, flat entrance doors
FD30S30 + smoke--Corridor doors (with smoke seal)
FD6060--Stairway doors, compartment walls
FD60S60 + smoke--Protected lobby doors
FD9090--High-risk areas
FD120120--Special applications
FD30/FD60 + insulation30/6030/60Where insulation criterion is needed
Fire Door Furniture and Ironmongery
  • Self-closing device: overhead closer (EN 1154 / UL 228) mandatory on all fire doors; min closing force per accessibility requirements
  • Intumescent strips: 10 mm x 4 mm or 15 mm x 4 mm strips in rebate or door edge; expand at 150-200°C to seal gap between door and frame
  • Smoke seals (cold smoke): flexible blade or brush seal at head and jambs; required for FD__S designations and IBC smoke doors
  • Hinges: steel butt hinges, minimum 3 per door leaf; no rising butts on fire doors
  • Locks and latches: must not compromise fire rating; typically tested as part of fire door assembly
  • Hold-open devices: electromagnetic hold-open connected to fire alarm; releases on alarm or power failure; door closer then closes door
  • Panic hardware: fire-rated panic bar or touchpad (IBC requires on assembly and educational exit doors for occupant loads > 50)
Glazed Fire Barriers

Types of fire-rated glass:

TypeIntegrityInsulationMax RatingApplications
Wired glass (6 mm)YesNo60-90 minObsolete in many jurisdictions; limited to small vision panels
Borosilicate glassYesNo60-120 minFire-rated vision panels, limited area
Ceramic glassYesNo60-180 minFire screens, spandrel panels, large panels
Intumescent gel glassYesYes30-120 minFull fire barriers, corridor walls, lobby screens
  • Integrity-only glass prevents flame and hot gas passage but radiates heat. Maximum area limited to prevent radiant heat exposure on escape routes.
  • Insulating glass (intumescent gel between layers) blocks both flame and radiant heat. Can be used for full fire barriers including in escape routes.
Firestopping (Penetration Seals)

Every penetration through a fire-rated assembly must be sealed with a listed firestop system:

  • Pipe penetrations: intumescent pipe collars (combustible pipes -- PVC, PE, PP); mineral wool + intumescent sealant (metal pipes with insulation)
  • Cable penetrations: intumescent block, putty, or pillows; cable transit frames for large cable bundles
  • Duct penetrations: fire damper (integrity only) or fire/smoke damper (integrity + smoke sealing); rated to match wall rating
  • Structural joints: fire-rated joint sealant (silicone or intumescent) with mineral wool backing

Cavity barriers:

  • Required in concealed spaces (above ceilings, within walls) to prevent unseen fire spread
  • Maximum distance between cavity barriers: 20 m in any direction (ADB); IBC Section 718 requires draft stopping in floor/ceiling spaces of combustible construction at max 280 m² (3,000 ft²)
  • At compartment wall/floor junctions extending into concealed spaces

Section 3: Means of Egress Design

Number of Escape Stairs

IBC (US):

  • Based on occupancy, travel distance, and floor area
  • Minimum 2 exits from each floor (with single-exit exceptions per Table 1006.2.1 for small, low-hazard spaces)
  • 3 exits for 501-1,000 occupants per floor; 4 exits for > 1,000

BS 9999 / Approved Document B (UK):

  • Single stair permitted for buildings up to 11 m (ADB) in certain occupancies with limited floor area and travel distance
  • Number of stairs based on maximum travel distance from any point to nearest stair AND stair capacity calculation
Travel Distances -- International Comparison

IBC (US), sprinklered:

OccupancyOne DirectionAny Direction
A--76 m (250 ft)
B--91 m (300 ft)
R--76 m (250 ft)
S-2--122 m (400 ft)

BS 9999 (UK), Risk Profile B1 (office, normal risk):

Escape RoutesOne Direction OnlyMore Than One Direction
Unsprinklered18 m45 m
Sprinklered27 m60 m

Approved Document B (England & Wales):

Purpose GroupOne DirectionMore Than One Direction
Office (2b)18 m45 m
Shop (4)18 m45 m
Assembly (5)15 m32 m
Residential (flat)9 m (7.5 m corridor)-- (single direction to stair in flat corridor)
Industrial (6)25 m45 m
Storage (7a)25 m45 m

Comparison note: UK travel distances are significantly shorter than IBC because the UK does not generally mandate sprinklers in the same way as the IBC (sprinkler credit is a specific extension of the base distance, not a near-universal requirement). When sprinklers are provided, UK distances increase but still remain shorter than IBC.

Stair Width Calculation

IBC method:

  • 7.6 mm (0.3 in) per occupant for stairways
  • 5.1 mm (0.2 in) per occupant for other egress components
  • Minimum stair width: 1118 mm (44 in) for 50+ occupants; 914 mm (36 in) for < 50 occupants

BS 9999 / ADB method:

  • Stair width based on number of persons per floor and number of floors served
  • ADB Table 5: for simultaneous evacuation, stair width accommodates total population minus ground floor
  • BS 9999 Table 13: discharge rates per unit width (0.6 m per person per minute on stairs at 1100 mm width)

Minimum stair widths:

StandardMinimum Width
IBC (general)1118 mm (44 in)
IBC (< 50 occupants)914 mm (36 in)
ADB / BS 99991050 mm (between walls, up to 150 persons/floor)
ADB / BS 99991100 mm (151-200 persons/floor)
DIN 18065 (Germany)1000 mm (residential); 1200 mm (public)
Protected Stairways

Escape stairs must be enclosed in fire-rated construction to protect occupants during evacuation:

  • IBC exit stairway enclosure (Section 1023):

    • 1-hour enclosure for 4 or fewer stories connected
    • 2-hour enclosure for more than 4 stories connected
    • Opening protectives: 1-hour doors for 2-hour enclosure; 0.75-hour or 1-hour doors for 1-hour enclosure
  • ADB protected stairway:

    • Walls: fire resistance equal to building's fire resistance period (30-120 min depending on height)
    • Doors: FD30S minimum (self-closing, smoke-sealed)
    • Ventilation: 1.0 m² natural ventilator at top of stair (or mechanical pressurization) for buildings > 18 m
Firefighting Shafts

Required in buildings > 18 m height (UK) or > 23 m / 75 ft (IBC high-rise):

  • Fire service elevator (fire lift): min 1100 x 1400 mm cab (UK BS EN 81-72); primary power + secondary (generator) power; waterproof elevator pit and landing; controls override to fire service operation
  • Firefighting lobby: min 5 m² (UK); fire-rated enclosure at every floor (2-hour walls, FD60S doors); contains dry/wet riser outlet
  • Dry riser: 100 mm diameter rising main with inlet at ground level and outlets at every floor; buildings 18-60 m height (UK). Fire service connects pumping appliance at ground level.
  • Wet riser: permanently charged pressurized system; buildings > 60 m (UK) or per IBC standpipe requirements (Class I in high-rise exit stairways)
Scissor Stairs

Two interlocking stairs within a single structural shaft, separated by fire-rated construction:

  • Each stair is independently fire-rated (1 or 2 hr) from the other
  • Separate smoke lobbies at each level for each stair
  • Common in high-rise residential where site constraints prevent two separate stair cores
  • IBC: scissor stairs are treated as separate exits only if each has independent exit discharge and the separating construction meets exit enclosure requirements
  • UK/BS 9999: accepted where demonstrated that failure of one stair does not compromise the other
Disabled Refuge Areas

Areas of temporary safety for persons unable to use stairs:

  • Location: at each floor landing of every escape stair (IBC Section 1009.3; ADB Section 4)
  • Size: minimum 900 x 1400 mm (IBC: 760 x 1220 mm / 30 x 48 in clear floor space) per wheelchair space; clear of stair discharge path
  • Communication: two-way intercom to fire command center / building management (IBC Section 1009.8)
  • Number: one per stair per floor minimum; two per floor if > 200 occupants on that floor
  • Not required in fully sprinklered buildings per IBC exception (occupants use elevator for evacuation under emergency evacuation plan)
  • Signage: International Symbol of Accessibility + "Area of Rescue Assistance"
Evacuation Strategies

Simultaneous evacuation:

  • All occupants evacuate immediately upon alarm
  • Standard for most building types (office, retail, education)
  • Total evacuation time must be less than available safe egress time (ASET > RSET)

Phased evacuation:

  • Fire floor and floor immediately above evacuate first
  • Remaining floors evacuate in sequence (above fire floor, then below)
  • Common in high-rise office buildings; requires voice/alarm communication system with zoned messaging
  • Requires at minimum: sprinklers, smoke detection, compartmentation between floors, voice alarm

Progressive horizontal evacuation:

  • Occupants move horizontally through fire/smoke barriers to an adjacent compartment on the same floor
  • Standard for I-2 (hospitals) and I-3 (detention) -- defend-in-place
  • Each smoke compartment must have capacity to hold its own occupants plus occupants from one adjacent compartment
  • Smoke compartment max 2090 m² (22,500 ft²) per IBC 407.5.1

Stay-put (residential):

  • UK residential strategy: occupants in flats not affected by fire remain in their flats (each flat is a fire compartment)
  • Fire-affected flat occupants escape via protected corridor and stair
  • Requires: fire-rated flat entrance doors (FD30S), fire-rated corridor/lobby walls, fire-rated stair enclosure, automatic detection in common areas
  • Post-Grenfell review: simultaneous evacuation capability being required alongside stay-put as a backup (Building Safety Act 2022)

Section 4: Structural Fire Protection

Fire Resistance Periods

IBC Table 601 (see building-codes SKILL.md Section 2 for full table)

ADB / BS 9999 minimum fire resistance periods:

Building HeightResidentialNon-residential
Up to 5 m30 min30 min
Up to 11 m30 min60 min
Up to 18 m60 min60 min
Up to 30 m90 min90 min
Over 30 m120 min120 min
Protection Methods

Concrete cover to reinforcement:

  • Fire resistance achieved by minimum concrete cover over steel reinforcement
  • 20 mm cover: approximately 1 hour FRR (depends on member type, loading)
  • 25 mm cover: approximately 1.5 hours
  • 35 mm cover: approximately 2 hours
  • 50 mm cover: approximately 3-4 hours
  • Governed by Eurocode 2-1-2, ACI 216.1, or BS 8110 Part 2

Intumescent coatings (thin-film for structural steel):

  • Applied as paint-like coating (0.25-5 mm dry film thickness)
  • Expands 20-50 times original thickness at 200-250°C, forming insulating char
  • Fire ratings achievable: 30-120 minutes (up to 180 min for some products)
  • Advantages: thin profile preserves exposed steel aesthetic; can be applied off-site or on-site
  • Limitations: requires controlled application conditions; some products vulnerable to humidity; maintenance access needed for recoating (25-year typical life)
  • Specification: dry film thickness (DFT) per fire rating, section factor (Hp/A) of the steel member; higher Hp/A (thinner steel) requires thicker coating

Board encasement:

  • Calcium silicate board (e.g., Promat): 15-60 mm thickness for 30-240 min FRR
  • Vermiculite/gypsum board: 12-50 mm thickness for 30-180 min FRR
  • Advantages: precise, consistent, factory-quality finish; can be installed in any weather
  • Limitations: visible box profile around structural members; time-consuming installation for complex geometries

Spray-applied fire protection (SFRM):

  • Cementitious (Portland cement + mineral aggregate): density 240-350 kg/m³
  • Mineral fibre (slag wool + cement binder): density 190-320 kg/m³
  • Typical thickness: 10-40 mm for 1-3 hours
  • Advantages: fastest application method, conforms to complex geometries, lowest cost per hour of fire rating
  • Limitations: rough finish (must be concealed above ceilings), overspray containment, cannot be applied below ~4°C, fragile if exposed

Concrete encasement (full):

  • Steel members fully encased in concrete
  • Provides 2-4 hours FRR depending on cover thickness
  • Heavy, expensive, rarely used for fire protection alone in modern construction
  • Still common where structural composite action (steel-concrete) is desired
Show full SKILL.md (1,591 more words)Show less
Mass Timber Fire Design

Charring method (Eurocode 5-1-2 / NDS/AWC):

  • Standard charring rate: 0.65 mm/min for softwood (spruce, pine, fir)
  • Charring rate for glulam/CLT: 0.65-0.70 mm/min
  • Zero-strength layer: 7 mm below char line (wood heated but not charred has reduced strength)
  • Effective residual section = original section - char depth - zero-strength layer

Design process:

  1. Determine required fire resistance period (e.g., 90 minutes)
  2. Calculate char depth: 0.65 mm/min × 90 min = 58.5 mm per exposed face
  3. Add zero-strength layer: 58.5 + 7 = 65.5 mm per exposed face
  4. Residual section = original - 65.5 mm per exposed face
  5. Verify structural capacity of residual section under fire load combination (typically dead + 0.5 × live, reduced from ambient design loads)

Type IV-A (encapsulated mass timber):

  • All mass timber surfaces protected by noncombustible material
  • Typically 2 layers of 16 mm (5/8 in) Type X gypsum board (32 mm total)
  • Gypsum provides ~60 minutes protection before charring begins
  • Total fire resistance = gypsum protection time + residual timber capacity

Type IV-C (exposed mass timber):

  • Timber may be fully exposed; fire resistance from oversized section alone
  • Architectural advantage: warm, exposed wood aesthetic
  • Requires larger timber dimensions to account for full charring

Section 5: Smoke Control

Purpose

Smoke is the primary cause of death in building fires. Smoke control systems maintain tenable conditions on escape routes and in occupied spaces during the time needed for evacuation.

Natural Smoke Ventilation (NSHEV -- Natural Smoke and Heat Exhaust Ventilation)

Sizing:

  • General rule: free ventilation area = 5% of floor area of the smoke reservoir, or 1.5 m² per 200 m² of floor area (whichever is greater)
  • Smoke reservoir depth: minimum 3 m (10 ft) from ceiling to bottom of smoke layer (maintain clear layer height above 2.5 m for tenability)
  • Inlet air: low-level openings at least equal in area to exhaust openings
  • Location: at highest point of smoke reservoir (roof vents, high-level windows)

Automatic opening:

  • Actuated by: smoke detection (most common), fusible link (thermal), fire alarm signal
  • Override: manual release at ground level and adjacent to ventilator
  • Fail-safe: opens on power failure (unless wind/weather concerns require closed default)
Mechanical Smoke Extract
  • Extract rate: determined by fire engineering analysis based on design fire size and smoke production rate
  • Typical rates: 4-10 air changes per hour for corridor extract; higher for atrium and large-volume spaces
  • Fans: rated for 300°C for 60 minutes (minimum) or 400°C for 120 minutes (for extended fire exposure); per EN 12101-3
  • Ductwork: fire-rated or within fire-rated shaft; dampers at compartment boundaries
  • Make-up air: must be provided to replace extracted smoke; typically low-level inlets at 75-80% of extract rate to maintain slight negative pressure in fire zone
Stair and Lobby Pressurization
  • Maintains positive pressure in escape stairs and lobbies to prevent smoke infiltration
  • Pressure differential: 50 Pa (0.2 in w.g.) with all doors closed (BS EN 12101-6); 12.5 Pa minimum, 87 Pa maximum (IBC)
  • Air velocity through open door: 0.75 m/s minimum (some codes require 1.0 m/s) to resist smoke flow
  • Fan sizing: accounts for leakage through closed doors, walls, and when one door is open on the fire floor
  • Door opening force: must not exceed 133 N (30 lbf) at the door handle with pressurization system operating (IBC 1010.1.3)
  • Compensation: variable-speed fans or pressure-relief dampers to adjust for doors opening/closing
Smoke Curtains and Fire Shutters

Smoke curtains (fixed or automatic):

  • Fabric barriers descending from ceiling to contain smoke within a defined reservoir
  • Deployed by: gravity (fail-safe), motor-driven from smoke detection signal
  • Drop time: typically 30-60 seconds to full deployment
  • Rating: per EN 12101-1 (D class for ambient smoke barriers, DH class for hot smoke)

Fire shutters:

  • Steel or composite rolling/sliding shutters providing fire separation
  • Rating: 1-4 hours (integrity); some provide insulation rating
  • Deployed automatically on fire alarm; manual override required
  • Used where fire doors are impractical (wide openings, service counters, conveyor openings)
  • Activation: fusible link (thermal), fire alarm signal, or both
Atrium Smoke Control

Atriums require specific smoke control analysis due to large interconnected volumes:

Steady-state plume calculation (simplified):

  • Mass flow rate of smoke: M = 0.071 × Qc^(1/3) × Z^(5/3) + 0.0018 × Qc (axisymmetric plume, NFPA 92) Where: M = mass flow rate (kg/s), Qc = convective heat release rate (kW), Z = height above fire (m)
  • For balcony spill plume (fire on floor below atrium, smoke spilling over balcony edge): mass flow rate increases significantly -- approximately 2-3x axisymmetric for same height

Design considerations:

  • Smoke reservoir at top: minimum 3 m depth
  • Exhaust: mechanical or natural (powered natural ventilators)
  • Makeup air: low-level, below smoke layer; velocity < 1.0 m/s to avoid disturbing plume
  • Plugholing: exhaust point must not extract air from below smoke layer; per NFPA 92 critical exhaust rate calculation
  • IBC 404.5: requires smoke control per Section 909 in all atriums

Section 6: Active Fire Protection Systems

Automatic Sprinkler Systems

Wet-pipe system (most common):

  • Pipes permanently charged with water under pressure
  • Activation: individual sprinkler heads actuate when ambient temperature reaches rated temperature (typically 68°C / 155°F for standard; 57°C for residential quick-response)
  • Response: only heads in the fire zone activate (not all heads)
  • Coverage: maximum 12 m² (130 ft²) per head for light hazard; 9.3 m² (100 ft²) for ordinary hazard per NFPA 13
  • Maximum spacing: 4.6 m (15 ft) between heads for standard coverage
  • Minimum pressure: 0.5 bar (7 psi) at the most remote head
  • Water density: 4.1 mm/min (0.10 gpm/ft²) light hazard to 8.1 mm/min (0.20 gpm/ft²) ordinary hazard Group 2

Dry-pipe system:

  • Pipes filled with pressurized air or nitrogen; water released when sprinkler head actuates and air pressure drops
  • Use: unheated spaces (parking garages, loading docks, freezers) where water would freeze
  • Delay: 30-60 seconds from head activation to water delivery
  • Maximum system size: 750 gallons per NFPA 13

Pre-action system:

  • Requires two triggers: fire detection AND sprinkler head activation
  • Single interlock: detection activates valve, then head must open
  • Double interlock: both detection and head activation needed simultaneously
  • Use: data centers, museums, libraries -- where accidental water damage is unacceptable

Deluge system:

  • All heads are open (no fusible element); water released to all heads simultaneously when detection system activates
  • Use: high-hazard areas (aircraft hangars, chemical storage, transformer rooms) requiring immediate total suppression
  • Requires large water supply

Residential sprinkler system (NFPA 13R / 13D):

  • NFPA 13R: for residential occupancies up to 4 stories (reduced coverage; sprinklers not required in closets, bathrooms < 5.1 m², attics, garages)
  • NFPA 13D: for one- and two-family dwellings (further reduced)
  • Quick-response heads: 57°C (135°F) rated, faster thermal response
  • Minimum flow: per NFPA 13R/13D hydraulic calculations
Fire Detection and Alarm

Detection types:

TypeDetection MethodResponse TimeBest For
Ionization smokeParticle ionization changeFast (flaming fires)Offices, corridors (being phased out in some jurisdictions)
Photoelectric smokeLight scatter/obscurationFast (smoldering fires)Bedrooms, corridors, common areas
Heat (fixed temp)Fusible element at set tempSlow (fires must grow)Kitchens, garages, dusty environments
Heat (rate-of-rise)Rapid temperature increaseModerateWarehouses, mechanical rooms
Aspirating (VESDA)Air sampling + laser detectionVery fastData centers, heritage, clean rooms
Flame (IR/UV)Infrared/ultraviolet radiationVery fastAircraft hangars, fuel storage
Linear heatCable changes resistance with temperatureModerateTunnels, cable trays, conveyor belts

Fire alarm zoning (IBC Section 907):

  • Manual pull stations: at each exit from each floor
  • Smoke detectors: in corridors, elevator lobbies, HVAC ducts
  • Heat detectors: kitchens, mechanical rooms, parking garages
  • Voice/alarm communication: required in high-rise, assembly > 300, certain E and I occupancies
  • Zone size: max 1858 m² (20,000 ft²) per zone; max 91 m (300 ft) length per zone; each floor a separate zone
Emergency Lighting

IBC requirements (Section 1008):

  • Illumination: minimum 10.8 lux (1 fc) at floor along exit access; minimum 10.8 lux at exit discharge
  • Duration: minimum 90 minutes from onset of power failure
  • Power: battery backup or generator

UK / EN requirements (BS 5266-1 / EN 1838):

  • Escape route lighting: minimum 1 lux at floor level along centerline, 0.5 lux at edges; uniformity ratio max 40:1
  • Anti-panic (open area) lighting: 0.5 lux at floor level throughout open areas > 60 m²
  • High-risk task area: minimum 10% of maintained illuminance or 15 lux (whichever is greater)
  • Duration: 1 hour minimum, 3 hours recommended (and required in many jurisdictions for sleeping accommodations)
  • Monthly functional test (flick test), annual full-duration test
Fire Extinguishers
  • Placement: max 23 m (75 ft) travel distance to nearest extinguisher for Class A (ordinary combustibles); max 15 m (50 ft) for Class B (flammable liquids)
  • Mounting height: handle at max 1525 mm (60 in) above floor for units

    18 kg (40 lb); max 1067 mm (42 in) for units > 18 kg on some interpretations -- verify with AHJ

  • Types: ABC dry chemical (most common), CO2 (electrical/clean agent), water mist (heritage), wet chemical (commercial kitchens)
  • Not a substitute for fixed suppression in buildings requiring sprinklers
Dry and Wet Risers

Dry riser:

  • Vertical pipe (100 mm / 4 in diameter minimum) with inlet at ground level and outlet valves at each floor
  • Fire service connects pumping appliance at ground inlet to pressurize system
  • Required: buildings 18-60 m height (UK ADB); IBC requires standpipe per Section 905
  • Outlet: 65 mm (2.5 in) landing valve in firefighting lobby or stair landing

Wet riser:

  • Permanently pressurized with water; fire pump maintains pressure
  • Required: buildings > 60 m height (UK); IBC Class I standpipe in high-rise stairways
  • Outlet: 65 mm (2.5 in) valve at each floor landing
  • Pressure: 7 bar (100 psi) at topmost outlet minimum
  • Water supply: dedicated fire water tank or connection to reliable public main with adequate flow (typically 1500 L/min for wet riser)

This skill provides general fire and life safety guidance for architectural design. All fire strategies must be developed in coordination with a qualified fire engineer and approved by the authority having jurisdiction. Fire codes and standards are jurisdiction-specific -- verify requirements against the locally adopted edition.

© Abhinavbwj, MIT. Rendered from Markdown: HTML in the file is shown as text, images as links, and headings moved down two levels. Raw file

Files

SKILL.md and 1 other file (references) in skills/fire-life-safety of Abhinavbwj/Skills-Architects.

  • SKILL.md
  • references/egress-design.md

Open the folder on GitHubat commit 30a0845

Compare with similar skills

Fire Life Safety next to the 5 skills that share the most tags, products or categories with it. Stars are the repository's; “used in” counts other GitHub owners with a copy.

Fire Life Safety compared with similar skills
SkillStarsUsed inTokensAuto-checkLicenceRepo updated
Fire Life Safety this skillAbhinavbwj/Skills-Architects296—~8.2kAutomated safety check: PassMIT
Python Type Safetywshobson/agents40k—~1.4kAutomated safety check: PassMIT
Author Expertisethedaviddias/Front-End-Checklist74k—~438Automated safety check: PassMIT
Safety Guardaffaan-m/ECC277k2 repos~554Automated safety check: NotesMIT
Safety Guardaffaan-m/ECC276k—~323Automated safety check: NotesMIT
Safety Guardaffaan-m/ECC276k—~255Automated safety check: NotesMIT

Similar skills

  • Python Type Safety

    wshobson/agents

    Python type safety with type hints, generics, protocols, and strict type checking.

    40k GitHub stars~1.4k tokensUpdated 6 days ago
    DevelopmentAuto-check passed
  • Author Expertise

    thedaviddias/Front-End-Checklist

    A skill your agent uses when auditing metadata, crawlability, structured data, or indexability related to Highlight author credentials and expertise.

    74k GitHub stars~438 tokensUpdated 5 days ago
    Marketing & SEOAuto-check passed
  • Safety Guard

    affaan-m/ECC

    Guard against destructive operations with three modes: Careful intercepts dangerous commands (rm -rf, git push --force, DROP TABLE) for confirmation, Freeze locks writes to one directory, and Guard…

    277k GitHub starsUsed in 2 repos~554 tokens
    DevelopmentAuto-check: notes
  • Safety Guard

    affaan-m/ECC

    本番システムでの作業時や、エージェントを自律的に実行する際に破壊的な操作を防ぐためにこのスキルを使用してください. An agent skill from affaan-m/ECC.

    276k GitHub stars~323 tokensUpdated yesterday
    Auto-check: notes
  • Safety Guard

    affaan-m/ECC

    使用此技能可防止在生产系统上工作或自主运行代理时进行破坏性操作。

    276k GitHub stars~255 tokensUpdated yesterday
    Auto-check: notes
  • JSON Safety

    thedaviddias/Front-End-Checklist

    A skill your agent uses when reviewing scripts, client components, bundles, or runtime behavior related to Parse JSON safely with error handling.

    74k GitHub stars~512 tokensUpdated 5 days ago
    DevelopmentAuto-check passed

More from Abhinavbwj/Skills-Architects

All 17 skills in this repo
  • Architect Calculators

    Abhinavbwj/Skills-Architects

    Seven command-line Python calculators for early architectural checks: area and density, U-value, daylight factor, egress, structural load, energy demand and cost.

    296 GitHub stars~3.4k tokensUpdated 4 mo ago
    Auto-check passed
  • Building Typology Reference

    Abhinavbwj/Skills-Architects

    Compares building types, from detached houses to supertall towers, using plan depth, density and efficiency metrics plus exemplar buildings.

    296 GitHub starsUsed in 1 repo~8.5k tokens
    Auto-check passed
  • Building Programming

    Abhinavbwj/Skills-Architects

    Guides architectural programming work: space needs, adjacency matrices, area schedules and net-to-gross checks for project briefs across common building types.

    296 GitHub stars~7.4k tokensUpdated 4 mo ago
    Auto-check passed
  • Architectural Concept Design

    Abhinavbwj/Skills-Architects

    Knowledge base for early-stage architectural design: parti development, massing studies, spatial organization and translating abstract ideas into building form.

    296 GitHub starsUsed in 1 repo~11k tokens
    Auto-check passed
  • Design Theory

    Abhinavbwj/Skills-Architects

    Architectural movements, design philosophy, critical theory, precedent analysis, and compositional principles for informed design reasoning

    296 GitHub starsUsed in 1 repo~8.5k tokens
    Auto-check passed
  • Material Selection

    Abhinavbwj/Skills-Architects

    Architectural material properties, durability, sustainability, specification, detailing, life-cycle assessment, and material palettes for building design

    296 GitHub starsUsed in 1 repo~8.4k tokens
    Auto-check passed

Questions about Fire Life Safety

What does Fire Life Safety do?

Comprehensive fire and life safety design expertise covering fire strategy development, compartmentation and fire barrier design, means of egress design including travel distances and stair sizing…. Fire Life Safety is an agent skill from Abhinavbwj/Skills-Architects. Comprehensive fire and life safety design expertise covering fire strategy development, compartmentation and fire barrier design, means of egress design including travel distances and stair sizing, fire resistance ratings and structural fire protection methods, smoke control systems (natural and mechanical), active fire protection systems (sprinklers, detection, alarm, emergency lighting), fire door specifications, and fire strategy coordination between architect and fire engineer.

How do I install Fire Life Safety in Claude Code?

Run `npx skills add Abhinavbwj/Skills-Architects --skill fire-life-safety -a claude-code`. Or copy the skill folder (skills/fire-life-safety in Abhinavbwj/Skills-Architects) into .claude/skills/fire-life-safety in your project. Claude Code loads it when a task matches its description.

How do I install Fire Life Safety in Codex?

Run `npx skills add Abhinavbwj/Skills-Architects --skill fire-life-safety -a codex`. Or copy the skill folder (skills/fire-life-safety in Abhinavbwj/Skills-Architects) into .agents/skills/fire-life-safety in your project. Codex loads it when a task matches its description.

Can I use Fire Life Safety in Cursor, Gemini CLI or GitHub Copilot?

Cursor, Gemini CLI, GitHub Copilot and OpenCode also load SKILL.md folders. With the skills CLI, run `npx skills add Abhinavbwj/Skills-Architects --skill fire-life-safety -a cursor` (or -a gemini-cli, github-copilot or opencode for the others). To copy it by hand, put the folder in .cursor/skills/fire-life-safety, .gemini/skills/fire-life-safety, .github/skills/fire-life-safety and .opencode/skills/fire-life-safety in your project.

What does Fire Life Safety need to run?

SKILL.md names no scripts, command-line tools or credentials: Fire Life Safety is instructions for the agent only.

Does Fire Life Safety access the network?

SKILL.md contains no URLs. Any network use would come from the scripts or tools the agent runs. This is read from the text; nothing was executed.

Is Fire Life Safety safe to install?

Our automated static check of SKILL.md found no risky patterns, such as piping downloads into a shell, reading credential files or hidden Unicode. It is not a guarantee. Review the folder before installing.

What licence does Fire Life Safety use?

Fire Life Safety is published under the MIT licence (the repository's licence). It allows redistribution, so the full SKILL.md is shown on this page.

How many tokens does Fire Life Safety use?

About 8.2k tokens (SKILL.md is roughly 33k characters). Agents keep only the skill's name and description in context until a task matches; then they load SKILL.md in full. Its references folder adds about 6.1k tokens, read only when the agent opens those files.

What are the alternatives to Fire Life Safety?

Skills that share tags, products or a category with Fire Life Safety: Python Type Safety (wshobson/agents, 40k stars), Author Expertise (thedaviddias/Front-End-Checklist, 74k stars), Safety Guard (affaan-m/ECC, 277k stars) and Safety Guard (affaan-m/ECC, 276k stars). The comparison table on this page puts their stars, adoption, token cost, safety result and licence side by side.

Who maintains Fire Life Safety?

Abhinavbwj (a GitHub user) maintains it in Abhinavbwj/Skills-Architects, which has 296 GitHub stars. The repository holds 17 skills in this directory. The repository was last updated on May 20, 2026.

Source: Abhinavbwj/Skills-Architects on GitHub. Facts on this page come from the repository at the commit we read; the author's words are quoted as theirs.